Fuses Stop Electric Shocks? Wrong! How to Teach Earth Wires

preview_player
Показать описание
I have to admit that I did not know this before I filmed this video.

Thanks for watching,

Lewis

_____________________________________

MY PHYSICS WEBSITES
Find even more videos organised by exam board and topic at:

GCSE Physics Online
A Level Physics Online

MY YOUTUBE CHANNEL
Your support in watching this video has been invaluable! To contribute towards the free videos on YouTube, make a small donation at:

FOLLOW ME

#electricity #alevelphysics #physicsonline
Рекомендации по теме
Комментарии
Автор

Current takes all paths. The element has actually lower resistance. A 3 kW kettle has just 19.2 ohms. However, while the kettle uses 13 A, only 0.1 A can kill. Also the wire can get completely loose so that it does not connect to the heating element.

The earth wire does not go to the earth on a TN system. It goes to the transformer via a copper connection. On a TT system it goes to the earth but then the resistance is so high that it does not blow the fuse. On TT one must have an RCD to make it safe.

One should abandon the term "earth wire" and use the proper term the CPC (The circuit protective conductor). That tells what it does without giving false implications how it does it.