Within this tutorial, we demonstrate the procedure for troubleshooting a "Device no response" message that appears when the HMI can still communicate with the PLC.

Given this scenario, a "Device no response" message may occur due to any of the following reasons:

- An incorrect data type may have been configured within the format tab of the numeric object. If for example, the register that you are reading occupies one word within PLC memory and the data type is configured such that HMI polls 2 words from the PLC. A communication error may occur.

- You may be using the wrong register type for the device register that you intend to read. For example, if you are communicating with a Modbus device that does not support Modbus function code 16 (decimal) and you use the 4X address type within our software, you will likely experience a communication error.

- A register used within an object may not have been used or made accessible within PLC memory or when using a tag-based PLC the tag name may have been changed within the PLC project.

- If the HMI has a bad connection due to a faulty Ethernet or serial cable or if the flow of packets is restricted due to an issue with a router or switch. The HMI may only display several objects at a time.

- It is also possible that “emi” noise may disrupt the HMI’s ability to communicate with a PLC or external device. In this case the issue may be resolved by using a shielded cable and a ferrite core if necessary…

#Weintek #PLC #HMI #EasyBuilderPro #Troubleshoot
Рекомендации по теме
Комментарии
Автор

Hello sir, i have problem when communicate TK6102i with CP1E N30S1DTD, how to connect DB9 to solve it?

AgustinusWahyuNugroho
Автор

I got this message "PLC Not Response", in this case my PLC is H3U-3232MT and HMI from WeInview. How to fix this ?

maksudiindrarukmana
Автор

How can l calibration weintek mt6070ih screen

atifbrema
Автор

I need to connect a CLP FX3U, China, with the MT8071IP via RS485, is there any tutorial?

elitonpavezi
Автор

I still have "device no response" on my hmi using omron plc. Could you please help me

nasibakarowuenak