How to set up or confirm the Full Scale of a Vortex Flow Meter from TacticalFlow Meter

preview_player
Показать описание
How to set up or confirm the Full Scale of a Vortex Flow Meter from TacticalFlow Meter

The password to adjust these parameters is 22 and we will work with the basic settings for full scale and units.

There are TWO buttons on the top of the Vortex Meter Display board, at abut 11 and 1 on the clock.
Left Click to change screens and when the Password shows up LONG hold the Right Button to invoke the input and use the Left button to advance the number to 2 and when that is in use the Right button to move to the second digit and advance with the Left button to the number 2. When you see 22 LONG hold the Right button and you are in the edit mode.

Call (831)-244-8080 for questions

Menu details:

MENU 22
Q Unit -- l/m
Q Mode -- Qvw actual (We are measuring volume flow....)
Q Factor -- 2121.47 Do Not Change (This is stamped on the side of the meter)
Density -- 875 kg/m3 (Water is 1000)
Q20mA -- 250 (FULL SCALE... If your meter is 250 l/m)
Q Cut-Zero % -- 5
Q Up Al -- 250 to turn the alarm on at 100%
Q Dn Al -- 25 to turn the alarm at 10% flow
Damp S -- 6
Comm Address -- 0
Clear Q -- Clears Totalizer, Password = 70

MENU 33
Language -- English
Pulse Type -- F_adj
Pulse Factor -- 0.01
Comm Param -- 9600, No
Comm Switch -- ON
P_display -- MEASURE
Set Pc -- 0
P0-Ref -- 101.3KPa
T_display -- MEASURE
Set Tc -- 20 Deg C
T-TYPE -- Pt=100
Tn -- 20 Deg C
Environ-T -- -20 Deg C (-10 C is fine if you do not get them cold.)
Q-adj -- DO NOT change this setting

MENU 44
Signal-TYPE -- LF: DN40-500 Lqd
Gain -- G=9
VPP limit -- 100mV
Fre-Range -- 11=34-850Hz
Work Type -- Digital
an-noise TYPE -- ANS
Signal-Adj-Set -- FIlter 10 or OFF
50Hz Cut -- ON
K-LINE ADJ -- DO NOT change this setting

Tactical Flow Meter Vortex meter features LARGE LCD display, shows the Instantaneous Flow Rate, Total Flow, in user selectable units.

 Vortex Meter Specifications.
• Wetted Materials all 304 SS 
• Velocity Range: See detail below.
• Velocity Accuracy: +/- 1% of reading
• Repeatability of +/- 0.05% of reading
• 1/2" to 4" 150# ANSI Flange Connections, up to 12" available custom.
• LCD Display
• Temperature Accuracy +/- 1 Deg C
• Temperature:         
◦ Gas: -40°F (-40°C) to 482°F (250°C)
◦ Std Temp Liquid: -40°F (-40°C) to 662°F (350°C)
◦ High Temp Liquid: -40°F (-40°C) to 626°F (330°C)[Add $450]
◦ Ambient: -40°F (-40°C) to 131°F (55°C)              
• Power Requirement: 24 VDC, 15 Watts maximum;   
• 3.6 VDC Lithium C Size battery for intrinsic safety mode. Has LCD Display but no 4-20 or ModBus
• Output signals: Modbus RTU, 4–20 mA, and 0-1.0 KHz for flow rate indication
• Digital communications: Modbus RTU
• Max Pressure 1.6 MPa, 230 PSIG. (Custom up to 4.0 MPa 580 PSIG)
• Display: Flow rate, Total flow, Temperature, and Pressure
• Wiring connection to enclosure size: M20 x 1.5
• Factory Final QC Test Certificate
• Integral Electronics
• Electronics Enclosure NEMA 4X / IP67
Vortex Meter Velocity Ranges:
The Vortex meter has different minimum and maximum flow velocities it can measure based on the fluid type and meter size. Please note the values below for proper sizing of your meter. 
• Steam:
1/2” ANSI Flange: 4-70m/s or 787-13,800 f/m  or 13-230 f/s
1” ANSI Flange: 3-70m/s or  590- 13,800 f/m  or 9.8-230 f/s
2” to 12” ANSI Flange: 1.5-70m/s  or 30.2-13,800 f/m  or 4.92-230 f/s
• Gas: 
1/2” ANSI Flange: 4-65m/s  or 787-12,790 f/m  or 13- 213 f/s
 1” ANSI Flange: 3-65m/s  or 590-12, 790 f/m  or 9.8- 213 f/s
2” to 12” ANSI Flange: 1.5-65m/s or 300- 12,790 f/m  or 4.9-213 f/s
• Liquid: 
1/2” to 12” ANSI Flange: 0.2-10m/s  or 40- 1,968 f/m  or .66-32.8 f/s

View full spec sheet here.

Please subscribe to our channel and hit LIKE if this video helped you.