How to test 3-phase motor using MEGGER meter ? Winding resistance and insulation test.

preview_player
Показать описание
#megger #megger_meter #megger_test #motor
megger test 3 phase motor
insulation resistance test 3 phase motor
Fluke megger meter
winding Coil megger test
megger tester how to use it
megger testing procedure

Link for Tutorials for Electrical Technicians

Please Subscribe to Easy PLC Tutorials for more Videos and Tutorials
Рекомендации по теме
Комментарии
Автор

So should we connect the plus end of the megger to the body or to the winding? so how should the correct polarity be?

chnbrs
Автор

Firstly: What is the allowable value of the insulation resistance? Secondly: You must reverse the connections of your device, the positive terminal will be connected on the winding and the negative terminal on the the motor housing. Good luck!

yubachuck
Автор

What about spinning the motor to look for shorts? Video is good but I had a motor that blew a 200 amp breaker. We megged it and it looked good until we spun the shaft. That’s when the short appeared.

Joe.
Автор

How to test the winding insulation of a submersible motor using a megger meter(Rish insu 20 insulation resistance tester)

rajinmithra
Автор

Sir motor windings are connected in star or delta ? Bcoz there's no strip.

IK-quhw
Автор

Apart from this tests which one is insulation resistance (IR) test?

falgunpatel
Автор

Taking too much time. Out in the real world the production boss demands quick but accurate troubleshooting. I was an industrial electrician for 50 great years and NEVER removed jumpers on an POS IEC motor or wasted time measuring resistance from IEC motor coil to another. If a winding is shorted or grounded does not matter because motor must be replaced ASAP. Ran several 480 motors with 5 meggerohms from motor coil to ground. You placed one merger lead on a painted surface . A big no no . Must be clipped to ground screw or bare clean metal. Should tell people that merger voltage is supposed to be double the line voltage plus a hundred volts so you need a 1, 000 volt merger to properly measure a 480 volt motor. I own a nice 5, 000 volt merger that found grounds in several 4, 160 volt motors over the years.

garbo
Автор

Where are the equivalents to 7, 8 & 9 leads?? What kind of sorcery is this?

Idrathernot.
Автор

I don’t see a MEGGER. I see a FLUKE tester.

Joey-JoJo-Jr.
Автор

It is unnecessary to remove the star connection when doing insulation resistance test.

aldinandigodinez
Автор

Please explain with audio this is not useful.. can't understand for freshers

papakutty