Today some more AAON AC's RTU/PKG/MAU units are not working yet again. Come Along Shall We
Рекомендации по теме
Комментарии
Автор

2 nd one with the tripped rollout switch could have a cracked heat exchanger, inducer motor that is not working properly all of the time, high gas pressure, high winds entering thru the exhaust.

polishtheturdmickelson
Автор

Check your gas pressure in and out of the gas valve. Check amps on induce motors both wires to the motor. Had one pulling amps on one wire this caused low rpms. When the gas fired up it would have a woop sound then a boom.

actechformallyyomama
Автор

Had that same code on a 5 ton AAON this week here in Indy, outdoor air temp 2 degrees with a wind chill at -15 degrees below zero.Called Wattmaster.  My problem ended up being a bad space sensor, also known as a thermostat.After replacing that, then got a new trouble code with a discharge air sensor in alarm.Ended up being a bad modulating motor with the outdoor air dampers stuck wide open pulling 100% outdoor air.  The heat could not keep up.

shawnk
Автор

@7:14 I have come to learned that the MAU units are just fart fans in the restrooms lol evac units LOL wtf they have heat too?

geoffhoweth
Автор

I don’t have time to make YouTube videos (or the smarts) because I’m too busy following up after folks who act like you and who don’t know their ass from apple butter and blame their technical shortcomings on the equipment.
I bet you a Guinness that the meters you bought at radio shack, on clearance, still have the protective plastic on them.

I’m out

Mic drop.

jfrancis
Автор

cold day lol. I'll just leave this here (( "8°F" Feels Like: "-4°F"))

throttlebottle
Автор

call a service tech and get it fixed, instead of reset and run from the real problems

jamesmettert
Автор

Them units suck balls. Over engineered isn’t the word.

vicvillalta
Автор

Aaon units=fine.
Technicians that can’t troubleshoot= not fine.

Be real careful if the units have the modulating gas valve and variable speed inducer motor. They need to be set up just right or you’ll have rollout issues, incomplete combustion etc...

jfrancis
Автор

gas supply issue thats coursing low gas pressure coursing it to cut out and error out

TheWestMidlands