AAON HVAC Is Now Working.

preview_player
Показать описание
After working on the unit the unit started working the next day .

If you see a tool are something in this video that you would like to purchase.Try shopping on AMAZON for whatever you need through the links below.


This video contains an affiliate links, which means that if you click on the links and make a purchase, I'll receive a small commission. Thank you so much for watching!
Рекомендации по теме
Комментарии
Автор

thank's partner for sharing!!!! happy 4th...

jimbola
Автор

Units that have reheat control the discharge temperature at the evaporator that appears to be a fresh air unit

lfries
Автор

If anyone wants to see more AAON vids post in the comments below I have 7 of them on this property that I can give you some tips and tricks on how I figured them out .

geoffhoweth
Автор

I'd still have it checked before that compressor bites the dust. If it's not already on its way out

joeshearer
Автор

The 1st stage compressor looks to be overcharge by the amount of sweat around the body of the compressor. Check your running Load amps when it loads and unloads, compare them to the nameplate compressor amps. Also check your super heat and subcool to see if the TXV are feeding the proper amount of refrigerant in to the evaporator.

Yes, the sound you hear is the compressor loading and unloading, but it shouldn't sound that loud.
I'm guessing the TXVS failed or are failing and are feeding to much refrigerant in to evaporator and your liquid flooding the compressor.

Good luck

felipeluna
Автор

I hate aaon units.... working on an old r22 I got some questions

jamesgowgodofwar
Автор

That compressor is short cycling I have worked on Aeons a long time ago be smart to put a set of gauges on that circuit is this a fresh air unit does it have DDC controls it's so you can see everything that is doing they're complicated and a pain in the ass the issue is getting familiar with that piece of equipment a lot of mechanics want to ram and jam it and get the hell out of there all units have a sequence of operation that is what you need to know what is the sequence at startup and while the unit is running you said something about the compressor unloading scroll compressor don't have an unloader on them semi hermetic compressor do

lfries