PME SLIGHTLY HIGH?!?! #shorts

preview_player
Показать описание

Рекомендации по теме
Комментарии
Автор

Pablo’s only gone and pinched the meter this time! 😂

daveenglish
Автор

To measure ZE first of all you have to remove the main earth and test. What you conducted was zs at db with all parallel paths

Jay
Автор

PME only exists on the other side of the main fuse. It forms part of the DNO's supply and CANNOT be measured at a consumer unit.
Your measurement can however be used to calculate the PFC. So far as Ze this is merely an indication, if it fails here then it will only be worse with only the main.

johnbrown-sovz
Автор

Split con Sub-main, so Zdb rather than pme (Ze)??

matthewthomas
Автор

Chris Is this possibly a feed from a 3 phase supply in another building which has the main incomer!!! And this being a DB2??

mikewilkinson
Автор

The DNO aren't interested above 0.50 ohms, even though our readings should be less than. 0.35.. Also Ze is taken with the main earth disconnected from the MET..

jonnyduncan
Автор

That’s a good tester we don’t have in North America

luisspacehomesconstruction
Автор

Did you null your leads. Also carry out Ze and PFC test using high current setting on meter instead of no trip setting. Remove parallel paths and I would also agree it is either an illegal main or a sub main from elsewhere as there is no meter installed!

JCR
Автор

Can you do Video going through test and expecting result and what range should be watch out from

wolverine
Автор

Is that incomer Tuf sheathed cable? 2 CU’s is the one to the right the sub board? All so confusing.

Tryingtimes
Автор

Orales interesante tu video, y tú multimetro es genial, dónde puedo conseguir uno así soy de 🇲🇽

jesusjacceb
Автор

That cut out has a link bar between neutral and earth so may be a TNS set up. Need to take neutral cover off to check

nickhuk
Автор

if you Disconnect the incoming earth and use crocodile clip readings would be just right

edmondhodaj
Автор

Imagine how high that reading could be if done correctly

dannyboisparky
Автор

Где взять такой прибор? Я так понимаю сопротивление контура заземления измеряет!

РоманХажиахметов
Автор

Better get the DNO to take a look at it.

UCCLdIkRECGtaGmoqO-TQ
Автор

suppose to do it on hi current 2 lead test.
where the meter is this an outbuilding

asamitchell
Автор

Doesn't really matter when you have rcbo's I'd leave it as it is, Dno never interested & still safer than an unstable rod.

smiffysmiffy
Автор

It sure looks like that db is connected to the cutout with no meter ????

persona
Автор

you need to switch off and disconnect the
main earth and test to avoid parallel paths

KDC_Electrical