Short video showing horizontal wet venting according the Uniform Plumbing Code, section 908.2.
Рекомендации по теме
Комментарии
Автор

I thought that tying in any other fixture to the horizontal wetvent was prohibited? The trap would need to tie in downstream of the vent, no?

CitizenShane
Автор

Excellent audio - really making full use of the A/V technology... 50% there anyway!

aquacruisedb
Автор

I would love to see a video showing how you modeled it in SketchUp! cheers

RossWilliamsDC
Автор

Do the WC and Tub trap arms have to connect to the wet vent at 45 degree above the horizontal plain of the pipe? Or does this only apply to dry vents? Thanks

deepbluespear
Автор

In the UPC there’s a 6 foot distance limitation from the flange to the vent - would this be the length of the green pipe, or the length of the green plus blue pipe?

maxslomoff
Автор

All this fails inspection in Kentucky.

phillipkirby
Автор

Just wondering if this setup would still follow the 2020 UPC? I might be reading it wrong, but isn’t the wet vent portion supposed to be upsized by 1 pipe size?

remodelingjunkie
Автор

I want to do something similar to this but was told it was a flat dry vent? any thoughts? anyone i can email my sketches to?

blahsaysmeu
Автор

True Circuit vent can serve up to 8 fixtures

cashk