Starting a VFD with 2-wire Start

preview_player
Показать описание
#accesstopower #AccessElectric #MotorControls
In this episode, we show you how to start a VFD Drive using the 2 wire start mode. In this example, we are using an Allen Bradley Powerflex 4, but you could use just about any drive and accomplish the same thing. For this drive, we had to set parameter 36 to enable the 2 wire start command. In a different drive, the parameters will also be different, but almost any other drive will be able to do the same thing. You will need to refer to the literature that came with your drive to set up the parameters correctly.

We then show you how to use a standard 3 wire start-stop circuit with an ice cube relay to start and stop the VFD Drive. We also discuss some best practices for how to protect your drive by wiring the start-stop power through an auxiliary contact on the motor disconnect.
Рекомендации по теме
Комментарии
Автор

I am a retired Journeyman Electrician. My son is getting into an apprenticeship soon. He and I will be watching your channel. Good job, Thanks.

WireMan-rgkc
Автор

Your Way of explanation is awesome. By watching many videos of yours it cleared my some concepts of control wiring. Many newbies are getting benefits from your vast experiences. Thanks a lot. 😊

shakirirfani
Автор

Wow, this was one of the better videos I've seen on setting up the AB PF4. Thanks.

irwinjimenez
Автор

I see; I forgot about this part 0:56. When I saw the blue wires coming from the ice cube relay I thought you were actually sending voltage to the terminals on the VFD. Thanks for your reply! Your videos are very helpful.

Idrathernot.
Автор

Very good explanation. So your recommendation is to have an auxiliary contact in the service disconnect to shut of motor/ VFD.

Aesthetic_person.
Автор

Wish you could of zoomed in on the terminals and powerflex it will gave a better view/idea of the whole thing but great stuff!!

usbaldorangel
Автор

You make some of the best videos brother. Keep on making videos. Thanks

lukestrange
Автор

Make sure when dealing with these your start signal type is set properly i just did a 523 about an hour ago and had to factory default it to allow me to move the start (2 wire) to 02/common(11) start config was on program p046 p048 p050 all had to be set to start signal 2 i.e. pin 2 and common to make the forward start possible.

jesseready
Автор

This would be much more better if shown together with its circuit diagram for easy circuit


Good explanation

augustmushi
Автор

another damn good video. wish there were more. thank you sir

brady
Автор

Thank you for posting and explaining the setup. I have an old 3 phase saw that I'm restoring and it looks like this set up would be a great way to use the existing old relay controlled start/stop switch. Could you post a link for the Ice cube relay and 110 switch? So I can purchase the same setup. Thanks again!

stevenschenck
Автор

I'm trying to use the same principle for siemens micromaster 420 invector but is not working, Please help me out.

jamesbaffoe
Автор

How can we change the standard function of a VFD terminal using parameters only.
Eg, making a moter to rotate in reverse direction by giving the command to the forward terminal (02).
I'm using powerflex 525 VFD.
Ps interchange of wire connection is not the option it has to be done by changing some parameters only.
Please help!

RahulGupta-ylgf
Автор

Hey teacher i would like to ask you a question, how long can I run a 24vdc loop for estop from control strip in VFd with two wire control? Thanks

alfredojuarez
Автор

What did yo use to power vfd I bought 3 phase do I need inverter now or how to power it up from 120V household?

nukeelda
Автор

Can you show us how to manually run a motor with a drive

Roelyize
Автор

so 8 and 6 are going to the VFD, does one of those have 24+ to its terminal?

williams
Автор

were you using 110v for terminals (11 and 2)?

Idrathernot.
Автор

Hi I am from st Martin I have a 110 motor connect to a drum switch for forward stop and reverse.the thing is the drum switch get worn out like six months so I want to know if you can show me how to wire 3 push buttons forward stop and reverse .i have an extension cord that I hook up to the drum switch where I get my 110 volt I would like to know if the same principle can work with the push button please help me out if you can

sarfrazally
Автор

Thomas Brian Harris Edward Garcia Helen

JustinVanhouten-pl