Bryan with HVAC School goes over AC pressures, subcooling, and superheat in his troubleshooting mindset presentation from the BTrained HVAC training event in Birmingham, AL. Bryan also talks a bit about his educational photo-sharing app, MechPic.

The suction pressure and suction saturation give us an idea of the refrigerant’s boiling temperature. Evaporation happens at the surface and not necessarily at the boiling temperature; on the other hand, boiling happens throughout the entire substance and occurs at the boiling temperature. So, the “evaporator” is really a heat absorber where boiling occurs.

A rule of thumb for suction saturation is that it should be around 35 degrees below the indoor ambient temperature at 400 CFM per ton. That differential or temperature split, also known as the design temperature difference (DTD), is typically 30-35 degrees in high-humidity markets that use 350 CFM per ton like Florida and Alabama, where the conference took place. Lower suction pressures generally result in a higher DTD, and higher suction pressures usually result in a lower DTD.

When we look at head pressure, we’re actually learning about the condensing temperature over ambient (CTOA). The CTOA is the temperature split between the outdoor ambient temperature and the condensing temperature. In general, CTOA tends to fluctuate a bit more than evaporator DTD, but a rule of thumb is that it should be about 15-20 degrees above the outdoor ambient temperature. SEER ratings may also affect CTOA.

A ratio of head pressure to suction pressure is your compression ratio. Higher compression ratios tend to lead to reduced compressor performance (moving fewer BTUs).

Even though we tend to see high head pressure as the main problem to avoid, we should be aware that low head pressure is possible. There needs to be an energy or pressure differential for matter to move from one place to another, and we’ll have trouble moving refrigerant if the head pressure is too low. The most important thing is to make sure that the system is working in accordance with its design.

Superheat is the degrees a vapor is above its saturation temperature, and it really tells us the amount of liquid that’s stacked in the evaporator. However, the evaporator and compressor superheat could be quite different due to heat gains in the suction line. Generally, we want to see 10 degrees of evaporator superheat (+/-5 degrees) on many AC systems. The TXV is supposed to keep superheat constant; however, some possible system problems can affect superheat beyond the TXV’s control (such as significant liquid line restrictions, though there are exceptions to that example).

On the other side, subcooling refers to the temperature of a liquid below its saturation temperature. In an HVAC system, subcooling indicates how much refrigerant we’ve “stacked” in the condenser; lower subcooling indicates that we have little liquid refrigerant stacked in the condenser, and higher subcooling indicates that we have a lot of liquid refrigerant stacked in the condenser. (There can, but not always, be temperature drops across liquid line restrictions.) Refrigeration systems with receivers don’t necessarily have to rely on subcooling values to indicate refrigerant storage (a rule of thumb for residential A/C systems is typically 10 degrees +/-3). When we measure subcooling, we really want to know if we’re feeding the metering device a full column of liquid. If we want to increase subcooling, we can do that by reducing the liquid temperature via mechanical subcooling or increasing the condensing temperature. (However, we don’t want too much subcooling.)

When we use the manufacturer’s specs to set our superheat and subcooling, we might actually be reducing the equipment performance, so we have to know exactly what our goals are.

Рекомендации по теме
Комментарии
Автор

Been in the trade 24 years, I love listening to your videos before work during my work out or morning walk, knowledge is power. Your videos reaffirm my work. Please keep spreading the love - one day I hope to be at one of your seminars. God bless, your a legend to the hvac family.

mikaelg
Автор

I like these discussions because I can see my weakness in theory of operation and principals

mike-ypuk
Автор

It's very unlikely that you're going to ever read this Mr. Orr, but I have learned more from your & Craig's videos than on sites in Commercial jobs for a company & some of the residential ones as well, even after 4 years, If I could, I'd love to come to Kalos & really learn

roymedlin
Автор

Hi, Bryan. I appreciate you for the great works you guys are doing. I would like to know if you have an accelerated HVACR training program? Alternatively do you have a packaged and elaborated videos for a new technician? Trust you will give these questions a response. Thanks.

okayjacobs
Автор

Great video! I liked the idea of having a community chat, I need that app

ebfsystem
Автор

I have been looking for such types of videos before. Thanks from Bangladesh.

honestman
Автор

Very good seminar for the trade thank you for sharing 👍👍👍

alexanderreyes
Автор

HVAC school at min 17’21” you mentioned 20 degrees superheat is too high in a 10ft line set but Copeland minimum is 20 degrees to ensure no liquid comes back. I believe your compressor SH overrides Evap Sh in this example. If you want 10 degrees in the evap you could risk flooding back. So you asked if 20 degrees SH is good back at the compressor and that would be the least you’d want at the compressor it should be that or higher all depends on length of lineset

johnnya
Автор

Excelsior My Friend ! Smashing through all your Videos...
Cooling season if fast approaching and I'm all about Complete solutions found efficiently and professionally.

The-LongRoad-Home
Автор

This is enjoyable to watch but I appreciate a tighter lesson plan.

tmst
Автор

Boilerator, yeh, sounds good. We should stick with this!

deineroehre
Автор

I can never watch your videos enough even if it’s a repeat on the same topic that you have done before I always learn something new on a method of teaching other people through your videos.

As you grow and learn and improve in your industry I grow and learn and improve in my industry by watching your videos.
I want to become an HVAC instructor as I approach retirement in a local HVAC college and adopting your methods and style of teaching along with Ty and Craig and Chris combining all these styles and methods together will definitely excel my students and myself in a teaching and learning environment.
👍. Thank you for all your efforts and time involved in producing these videos so we can all share and pass the knowledge along

coldfingersub
Автор

I call that the mirror effect on subcooling it is the opposite of increase condesor temp for max flash and flow bubble point and flash and sat temp

KevinMartin-dpqf
Автор

Just because your name is Bryan doesn't mean you can steal Brian Regan jokes.

trevmint
Автор

thats why its called vapor phase refrigiration, because the gas relies on vaporizing, not boiling, because rf 134 boil at -180

alish
Автор

What about mini splits that use EXVs? For instance, the techs at Mr Cool say you don't measure the superheat or sub-cooling because in their systems those numbers change constantly. They want to rely upon the suction line pressure.

basspig
Автор

Where would I start with you’re vids ? I’m an apprentice

luisvillatoro
Автор

Bit of trivia from hi-fi audio. Generally, they pitch is the amplifier has 30db and that means is amplifies the signal 30 times. It just so happens 30db is about 30 times. It's really 29.xx db, but it just happens at that point, 20 db is not 20 times, etc.

jkbrown
Автор

Early on you argus that the evaporator should be called a boiler because you think the phase transition is happening inside the liquid, but this is incorrect. The refrigerant is evaporating off of the surface of the droplets of the refrigerant that were created by the metering device. The surface area is immense at this point allowing it to quickly absorb the latent heat of vaporization.

leftover
Автор

Brian, can you share your powerpoint? I'd like to have this class with my techs.

Chubbadubz