Cable Size Calculation for Medium Voltage or 11kV Electrical Systems

preview_player
Показать описание

Рекомендации по теме
Комментарии
Автор

Thanks for making this video. It's the best I have found on this topic. Can you please provide info on how the reference materials used on this video? The derating factors and cable size tables will be especially helpful.

olalekanmagbade
Автор

Thanks for sharing these valuable details.

Kindly send the link to get this chart.

amiselectricals
Автор

de rating factor reduces the current carrying ability of the cable, so 187A x 0.76 = 142A, as the FLA of transformer = 131A, selection of the cable size of 50sq.mm is good. correct me if iam wrong.

karthickd.n
Автор

Do you know about any software for a medium voltage cabling calculations?

foras
Автор

It would be helpeful if you share the standards you're taking into account

juanlotta
Автор

what is the difference between HV and LV cable sizing?

charinath
Автор

Thanks for share verry interesting content

sniperchanel
Автор

where can i find correction factor tables? thnx

keyable
Автор

How to calculate if we want to use 2 or 3 nos of cables per phase?

hidayahsahudi
Автор

how can u add Rcos@ and X sine@ .these are complex numbers. it should be

sumedhaweb
Автор

Very Good. Keep it up. Make more videos.

faisalbukhari
Автор

hi sir, i gave one doubt if the length is 15000 MTR as my able length is 15KM shall i need to divide it my 1000 or 10000..

azhar
Автор

Hello! May I ask the references for the derating factors Tnx

dank
Автор

Could possible to share supporting documents

ScholarshipTamil
Автор

can you please share the excel sheet for the easy calculation for pakistan.

saeedahmed
Автор

How many transformers can feed from m v switchgear in one loop

mohamedali-txsb
Автор

from where you get the cos@ & Sin@ value? respectively 0.8 &0.6 please clear.

zubairali
Автор

Hello Sir, what are you showing the tables to calculate HV/MV Cables from which IEC Code?

thrinadnadh
Автор

Hi H N, As I have known for the motors, we should be aware of voltage drop in both steady state & starting of motor. Could you explain for these cases of Motors?

tuleanhvt
Автор

Could you please advise how we can find the Max. Load Allowed on 1 Feeder @ HT = 5MW or 6.25MVA or 328A?

foras