Cooling Coil load calculation using Psychometric chart

preview_player
Показать описание

Рекомендации по теме
Комментарии
Автор

Thanks. Good explanation. We use British units over here in the US. But, still very helpful.

mustangsandwich
Автор

sir how is it possible that outside air DB is 41 and WB is 87 centigrade? not cleared that part

hamzatariq
Автор

This assumes that all the air is cooled to 12.7 C saturated. In real life only part of the air volume gets in touch with the cooling coils which would be at a T lower than 12.7 (and therefore cools down to saturation point). This will mix with the remaining air volume and therefore the final point for the entire air volume is somewhere in the middle. You don’t supply air at 100% RH to a room.

paoloesposito
Автор

Sir please make a video on how to calculate U value for heat load

sarvendragusain
Автор

you divide volum flow rate ( m3/min ) with specific volume ( m3/kg ) should you get mass flow rate in kg/min instead of kg/s ? since you are using perminute so Q out is kw/min not kw/h correct ?

achristan
Автор

sir why you take 50% RH? you not considered WB 87 centigrade

hamzatariq
Автор

Sir plz calculate capacity of cooling coil using mcquay psychrometric analyzer

ompathak
Автор

If the air at dry bulb temp at 36 deg C and RH at 42 %, can i cool the air at 11 deg C by directly adding chilled water into air through evaporatorive cooler.
What will be the required sprayed chilled water temp and flow rate?
Can we use chilled water at 7 deg c
And what is the chiller load TR of makeup chilled water?

SanjayYadav-fydg
Автор

I think the calculation is wrong if first the Flow rate is in M3/min and not M3/s. if you multiply (H1-H2)* Mass flow rate, we do not get the same result as you. Can you please clarify.

ramynazzal
Автор

In HAP generated report it shows that 4.9 ton coil load is required, then why did you calculated it by manual method.it is my doubt, if u can please tell me

haarimangat
Автор

why you chosen 50% RH
From where you bring this number boss ?

momolove
Автор

i did calculation by your metod but answer comes wrong and have checked your answer which is also
wrong .

hamzatariqdhanyal
Автор

we can calculate fresh air using HAP, why psychrometric

ahmedshafath
Автор

Hi, you made a mistake. 34.72 m3/min / 0.925 m3/kg = 37.53 kg/min and not kg/s ;)

bernardlaval
Автор

Wrong concept, It is easily understandable your line is crossing outside of 100% RH, which is not possible.Pls haveva proper knowledge before you put video on youtube.