Calculating Motor Overloads

preview_player
Показать описание
This video walks through the steps to calculate the maximum overload setting for an individual motor using the 2015 Canadian Electrical Code. This is not an installation guide, and local inspection authorities should always be consulted.

Feel like buying Chris a coffee? Think of it as SchulerRuler fueler!

Рекомендации по теме
Комментарии
Автор

Over ten years in the industry and your video just cleared many unanswered questions. I like your method of explaining. thank you.

dwaynecampbell
Автор

Appreciate the refresh. All journeymen/women should take some time to review their knowledge base. The field is so diverse and its easy to get stuck doing the same things for a while, which leads to important aspects being forgotten.

Congrats on the channel.

toumistra
Автор

Thank you very much for sharing with us.

Mahle-fb
Автор

I don’t know where will I need this info but you are a good teacher sir 😀

roseandmose
Автор

...Excellent video, I've been trying to explain this simply for my road techs...this is the BEST explanation I've found....Cheers man.

angusandleigh
Автор

This was SO helpful for the program I am doing! Thanks for the great class!

thecartoongirl
Автор

Great class, very good explanation and well paused. appreciated !

nogarats
Автор

Great class! Thank you. It helped me a lot for preparing to take my challenge exam.

williansousa
Автор

You teach so well. I'll try to support through views and likes. Thanks for making informative videos likr this. 👏😃

rg
Автор

Excellent explanation! Your explanation is clearer than my future JK hehe nice video.

revertedakhi
Автор

wait, how the hell can you write backwards so flawlessly

trevorrichardson
Автор

I'm trying to calculate an ISO or German motor with a cosine of 0, 95 ~ My understanding is that "european" motors are basically at factors of 1 on down to 0.85 or so which isn't very efficient. So if the motorplate says AMPS at 3.4 ~ with a cosin of 0.95 I would set my overload "at basically" 3.4 Amps IS THIS CORRECT?

brentbarnhart
Автор

Great vid. Can u explain difference between HOT state and COLD state of a thermal overload relay, thanx

RizwanKhan_
Автор

Hello Sir Thanks for your videos, found really helpful.
I need electrical codes book ?

muzammilahmed
Автор

Studying to challenge my third block and these videos are so helpful. If you have any tips for third year code, I would be beyond grateful. Thanks for doing these!

matthewmacpherson
Автор

you should do welders section 42 calculations in there

bfg
Автор

If I have A 30 HP, 600 V, 3 Phase squirrel cage motor feed from autotransformer and is controlled by a Star-Delta starter. What is the maximum size inverse time circuit breaker allowed to protect the circuit.
Is it based on phase current like the above video showing?

nadirgabir
Автор

@schulerruler Hi. In case of Y/delta motor, the overload relay will be installed after the main contactor?

karimeldaly
Автор

Why Y/ ∆ start using phase current, while other motor using line current ( FLA )???

thekhang
Автор

Can you suggest some sources me to learn basic of these terms

roseandmose