NEC Motor Load Calculations Example

preview_player
Показать описание
Example calculation for motor calculations per the national electrical code.
Рекомендации по теме
Комментарии
Автор

I took this guys full prep class a few years ago. Passed my masters exam on the first try thanks to it! great teacher

Sincoola
Автор

Very well laid ou, t with Code articles as references. Nice job!

soundman
Автор

Information is thrown out very thoroughly. Thumbs up!

TheMadhatter
Автор

The overloads are calculated at nameplate FLA, right? Everything else is calculated from the FLC from from 430 tables, am I right about this?

stevenwarren
Автор

Your videos are great. Please do more ..

JesusCruz-wtzp
Автор

Great example!! Way to walk through it!

controlsgirl
Автор

Why do you always use 75C degrees column for motor feeder wire size? (8:30 in video)

daltondelaney
Автор

Thank you so much about to go for my exam shitting bricks this helps so much

kylecropanese
Автор

I've noticed you use 75° column for the branch ckt conductor size. However I was told to use 60°C column for circuits rated 100 amperes or less (per NEC 110.14-C) regardless of conductor insulation rating. Was there an exception that I missed?

Luminous
Автор

wouldn't the feeder size in step 5 be calculated as THWN-2 like the motor wires? And thus be a number 6 wire rated for 75 AMPS? Great video though, thanks

EbagOmocaigid
Автор

Service factor is 1.4 and the code is 1.5 or grater to be × 125%. If is not 1.5 por greater it should be × 1.15.

juliorojas
Автор

i have same question as others on using 75C when ampacity column. 75C can be used only when terminations are also 75C. why is 75C used here?

BobbaFett
Автор

When you size breakers for motors, wouldn’t you round down to the next standard circuit breaker size?

mcarroll
Автор

On step #3 if its THWN-2 at 9.5 amps wouldn't the answer be 18 for copper? Or is it 14 because of the temp rating? Confused. I understand how you got the answer for the 65 amps just not the 9.5 amps.

MrTomObama
Автор

For Step #6, why wouldn't you add 150A to 20A for the remaining motor? Why did you only add the FLC and not the Branch Circuit protection from step #4 like you did for the larger motor?

MensLifestyle
Автор

Could you please tell me why the 40hp motor doesn't have any starter

thanmaysudev
Автор

Wouldn’t you size your OVERLOADS to your FLA on the motor? Not your FLC from the code book?

mcarroll
Автор

Where does table 430.22(E) fall in these steps? If asked for any of these rating percentages? Answer be helpful

Mike-eczp
Автор

You dont need the FLA to do these calculations?

Primez
Автор

I think you made a small mistake by multiplying your overload protection device with your FULL LOAD CURRENT instead of your FULL LOAD AMP??

oscarization