9 - Insulation Resistance Global Test - Hull College Electrical

preview_player
Показать описание

Рекомендации по теме
Комментарии
Автор

You can test at 250v DC if there are RCDs installed or you can do a combined line and neutral test to earth at 500v it will not damage RCDs or other sensitive equipment as there is no potential difference .

Dog-whisperer
Автор

Hi Lauri, When testing between L and N on the dead side of the RCD, is there a risk of damage to the RCD. When doing my 2394, our lecturer always warned us of not damaging the RCD when IR testing although I can't see how this would occur after looking at an RCD diagram. I always individually test the ccts. Many thanks.

davidlockett
Автор

Thanks. Preparing for my 2394 writing exam next week

Kitchentotaste
Автор

Not the best way to clip your croc clips!

nomorefaith
Автор

Dear sir,
I have a done a house hold wiring for villa, During a megger test we notice that valve between phase and neutral is good 500 Mohm when test between Phase to earth wire it is shown as less than 100 Mohm when i remove the all wire from conduit and we test it is showing correctly as 500Mohm, After that i replaced all wire as New before pulling the wire in conduit i checked it is shown correctly as 500 Mohm after pulled the wire in conduit it shown as below 100 Mohm Please give me solution,
Wire: National wire UAE
Tester:Fluke 1663 Multifunction Installation Tester(new)

tamilselvanin