Converting 480 volt 3 phase air compressor to 230 volt single phase with a VFD - 2 of 2

preview_player
Показать описание
In this second video I cover the actual wiring changes, insertion of new contactors, connection of the air compressor control system and VFD, how the VFDs are activated via the controller and a host of other goodies!

I hope it helps someone considering doing the same!

While most of our needs will vary, here are the parts I used.

Рекомендации по теме
Комментарии
Автор

Great info here, learned quite a bit and will refer back in the future. Subscribed, thanks!

bfqjimj
Автор

Thank you for sharing this. We are installing a screen printer and we need a 10HP with CFM of at least 33 / rotary screw with a dryer and our shop is running single phase. It's a challenge to find one that is a 10HP in a single phase. I talked to a sales rep who sells different brands, and he stated that we should not convert a 3-phase air compressor to a single phase as it will shorten the lifespan of the compressor. However, I am seeing folks converting compressors over and I don't see anything neg on doing it. My question though is, you've laid out a very detailed plan of doing it but if we are just going to be needing to convert and run 1 air compressor, is there easier way you would recommend, you mentioned something about a rotary converter. The compressor will be almost running all day at 33 CFM and I want to we do this without having issues, so if need to spend a little more to get something that will hold up to the daily use. What would you recommend? Thank you so much.

Bunker-Apparel
Автор

How much of a difference would it have cost to replace the three phase compressor motor with a single phase motor compared with that converter panel. I have an old three phase five hp compressor that I use to have in my shop years ago but don't have three phase power at my house that would like to hook up my old compressor again.

JohnnyCab
Автор

So i have an 80 gal vertical air compressor that is 220 volts 3ph. Motor is 7.5 hp and unit will do 25cfm max output. I do not need 25 cfm 90% of the time so i like the option of a VFD to be able to reduce speed and noise level . unit has a pressure switch and a starter no control board. from my understanding i would need a 15 hp VFD ? And would i still need the starter if i went with a vfd on a ramp up delay? Sorry for the questions i have been around VFD a little but never wired one.. this compressor was surplus and was free.

aaronandrson
Автор

Do you have part #'s for the contactors, bar and connectors?Facebook? Or a way to contact you besides facebook?

chipsammich
Автор

Do you know why the schematic had you loop the 3rd leg around to the bottom of the relay?

northlander
Автор

How can i run 2 air compressor with one VFD ???
At one time only one compressor runs..

yogendraambalia