Needed an extension cable for the hilariously short power cable on the Cut-Shifty... plus something so I can use it and the welder more than a couple feet away from the 220V outlet in the garage.

25 feet of extension cord should fit the bill. Let's make one.

Licensed under Creative Commons: By Attribution 3.0 License
Рекомендации по теме
Комментарии
Автор

YOUR "STRUGGLE" HELPED ME LEARN IT BETTER. THANKS FOR SHARING

NaLovePHATLife
Автор

First thing I made for my everlast welder was an extension cord so that I could use it 50ft away from the outlet. Good video my friend.

marksmith
Автор

Spit coffee through my nose during the intro to your video ... thanks for the laugh and the video. Very helpful. The out takes cracked me up, too. Maybe you're in the wrong profession? 😀 Thanks, man.

herblober
Автор

Hey Nate....make some new videos! I was really starting to dig your channel and your great explanations of how to do things....your humor was great too!

Fireship
Автор

The Mr. mom clip was perfectly placed! I made one of these extensions for my Cut shifty back in summer. It’s handy to be able to move the machine around and not stay tied to the wall. I made the ground clamp setup you featured in your other video and it’s working great! Glad to see a new video from you!

Fireship
Автор

What about 12/3 for "15.0 amp" 5hp Campbell hausfeld aircompressor for tire air? The tank holds 100 psi forever so no long run times. No air tools. 25 feet?

barefootinbriefs
Автор

I myself am a novice, nevertheless, I learned what I needed to know.
Thank you sir, and I've subscribed, as I liked your attitude and commentary throughout.

skipwilson
Автор

"IN THE BEGINNING" - it's sounds like a struggling, heavily constipated dude...

Enjoyed the vid, so I liked and subbed.

usernamemykel
Автор

Nate where can I buy an outlet and a plug male and female. Can you give me the website where I can order the parts that I need so that I can make an extention cored for my welding machine.. thank you very much..

ricardofredeluces
Автор

Nate. I'm amazed that you did an electrical video and had so few comments. Awesome! Three things, the #8 conductor is rated(in your configuration) 40 amperes, and a #6 is 55 amperes. So the conductor size is correct. The metal box that you used should be connected to ground. I do not believe you did. I do not understand why you used the metal box instead of the surface mounted receptacle. If you ha, no need for the second point. If someone tries to preach NEC they are incorrect. Cords with plug and receptacle are not premise wiring as the NEC is written for and stated in article 90. I'm sure the cord works very well! Enjoy life!

KevinCoop
Автор

Can I put 2 cords together to get where I need to

wilkincabrera
Автор

I would use red and black as hot. White and green wire ties together for better ground

KeithRatliff-me
Автор

Can I put cords together to get where I need to?

wilkincabrera
Автор

That intro. That’s me making a pigtail rn. Lol

twotatanka
Автор

A little confused... you say "white on narrow blade ". a minute later you put black wire on narrow blade..

moparny
Автор

Could you wire the extension directly into the breaker panel?

amealnet
Автор

I have a white cable black and red and a solid copper one with no color what do I do?

victorMartinez-pbgj
Автор

This guys pretty funny. Helpful video as well

spreadcreekjr
Автор

you are a funny guy, nice video, also at the end of the video I realize that the extension cable is way thicker than the welder cable.

zakarathedragonqueen
Автор

Finally got too see a video where they dont use the red wired i got a lincoln invertec 350v had a 4 wires green black white red the red one is not used when i putted this plug the hot wires are black and white and green led is the ground

jordanlerma