TBB BYPASS ASSIST FUNCTION

preview_player
Показать описание
BYPASS ASSIST FUNCTION

Grid will support the battery to power up the loads.

When will this function work:
1. If bypass setting is Enabled (27 - 1)
2. If actual battery voltage is not yet reaching the low battery alarm voltage (34)
3. If the load current from the battery is HIGHER than setting no. 59 which is the Battery Max Discharge Current

Example.

Actual Battery Voltage - 26V

Setting 34 -Low Battery Alarm Voltage - 24V

Actual Battery Discharge Current (Load)- 55A
55A x 26V = 1,430 Watts

Bypass Function:
50A will be powered by the battery until it reaches the setting 34.

5A will be powered by the Grid and/or Solar if available.