11 kV D.D.O. fuse explodes on a cable fault

preview_player
Показать описание
The HV cable was meggered and had one phase reading lower than the other two phases, although the 5 kV Megger didn't break it down fully.

A low amperage high tension fuse was used to test the cable and avoid risking tripping the feeder.

The fault developed as a phase to screen fault which was later traced and thumped. Fault found in the crutch of the PILCpart of cable in the.300 kVA transformer.
Рекомендации по теме
Комментарии
Автор

Translation of the technospeak: "We tested the power line and found that there was probably a short in it, but we weren't sure. We didn't want to test it with a normal fuse because that could have caused more important fuses to blow, so we used a smaller rated fuse than normal for the test. This is the fuse blowing, which told us the fault was real. So we found and fixed the fault which turned out to be in a transformer down the line."

melkiorwiseman
Автор

0:31 sounds like roblox death sound effect

KudxFrogMuSic
Автор

For anyone that doesn't know, that little swinging stick on the pole he was trying to push up, is called an expulsion fuse and it completes the circuit and allows power to flow again. The slightly bulky thing he was trying to push it back into what's called a cutout. If the voltage gets too high or there's some type of surge or fault, the fuse does something similar to what a circuit breaker in your house does, only instead of the switch popping to the "off" position, it blows up. :) Usually VERY loudly, as you can see here. LOL

EphemeralProductions
Автор

The boom noise is the actual fuse exploding and opening the circuit.
The pushing rod is called a hot stick or ddo fuse stick and is high voltage rated and made of fiberglass.

RODALCO
Автор

"I wouldn't touch that with a ten foot pole!" "Would you touch it with a ten meter pole?"

fartonaut
Автор

Is this anywhere near where either photonicinduction or Colin Furze lives, by any chance?

kaylamitchell
Автор

Correct, in this case the cable was faulty. In the industry a 5kV insulation tester / Megger is used. Sometimes a cable test reading is lower on one of the phases but not low enough to break down with test gear. e.g. 500 Meg. 450 Meg and 30 Meg ohms. obviously the lower reading most likely has a problem with it. To save time with an outage it is better to blow another 15 dollar fuse into the fault, and get a good fault which is easier to detect with test equipment.

RODALCO
Автор

The bang is always louder then you think even if you know the fuse is gonna blow.
More spectacular at night.

RODALCO
Автор

I thought I wanted to get trained to perform this work.. After doing more research & deep thinking, I was like maybe next lifetime. Kudos & much respect to everyone working in this field/ career. 💐💐

rayvolcy
Автор

On 11 kV cables we use 8 or 16 kV pulses to locate faults with a so called Thumper. to create an arc across the fault and pick up the noise with a listening set. Prior to that test the cable route is traced and marked out for its path.

RODALCO
Автор

it's a cable fault.
cable: i'm so sorry guys

sirisoj
Автор

They don't blow up randomly. This one blew up at a cable fault.
In your case a cable underground mat have faulted or a transformer.
Also there could have been road-works somewhere, and they struck a cable with a digger or drill.

RODALCO
Автор

My life in a nutshell; When you finally get control of things and go to the top, it all explodes and comes tumbling back down.

AceTheDragon
Автор

New Zealand is a colonie of the UK. The systems used in NZ are the same as in the UK. Also a lot of equipment originates from the UK, like Reyrolle, Brush, English Electric, Ferranti, Long&Crawford to name a few.

RODALCO
Автор

There is no gun powder in the fuse. It is the arc melting the fuse wire in a confined space ( the ddo tube ) and unlatching it from the source. DDO stands for Dominion Drop Out fuse.

RODALCO
Автор

The people that do this kind of work earn their money very dangerous job. Thank you for your service

robertcoogle
Автор

It went boom so loud! I'm scared! Where is my blanket and coloring book?!

hotrodhog
Автор

Review: Slow burn but the ending was explosive. 8/10.

jackkraken
Автор

Cable: Explodes
Man: *DEATH METAL SCREAM*

FROSHTVReL
Автор

When you play gta 5 in max settings
Your pc:

zohaibrauf