Found a switch with FASTON (spade) connectors being used in a bedroom recently 🤔

loosecannon
Автор

C3 for me. Labelling the cu "class 2 fitting only" is a must though

richnorman
Автор

Done thing when this was installed. Could be part of an earthed conduit system. Code it C3 and tell them to take those lovely stainless light switches and fittings off and put plastic or double insulated.

Nomenloony
Автор

It could have steel conduit to the back box for its Earth path.
Yes I suppose a little sleeve or tape even on the black core indicting the second switch line, but it was the 70s and it was ok do plenty of things we wouldn’t do now.

rossmurdoch
Автор

No CPC C3 if Nylon lugs throughout the circuit and plastic fittings throughout Lack of ID sleeving on conductors C3.

markstant-sqkb
Автор

at least he was thinking of the next man with the cable left

DreadyBob
Автор

It's a c3 code with class 2 accessories connected and c2 if class 1. 😜

Timetochange
Автор

There was no requirement to have a cpc when this was installed. It's fine.

TheDAMeaning
Автор

C3 for identifying conductors
C2 for no CPC. Be advising removal of any metallic fittings on that cirucit.

stephenllewekyn
Автор

Is the pvc sleeving a bit melted near the terminal? C3 for no cable indetification colour oversleeves. C3 for no CPC. Is it a plastic light fittings? Also backbax looks iffy, maybe the start or corrosion

sergiofernandez
Автор

Class 2 light switch and back-box has plastic threads. Guessing no CPC or screws missing lol. C3

jamesmoon
Автор

Did you turn of the lights? I'd be getting a rewire out of that for sure 😂

kearney
Автор

If you had a plastic backbox and faceplate and use nylon screws, would you need an earth?

walseee
Автор

C3 as per guide me referencing contact area of 3.5 screws

tomorichard