How to calculate short circuit current rating in transformer || Fault level calculation

preview_player
Показать описание
How to Calculate Short-Circuit Current:

First we must know these three values-
X-mer Rating = ?
Secondary Voltage = ?
% of Impedance = ?

Example:
X-mer Rating- 1500 KVA
Secondary Voltage- 480 V
% Impedance- 5.75%

Answer:
Formula:- (a) Isc = FLA / % Z Impedance
(b) FLA= KVA / (√3)×(kVsec)

Put the value in this formula
FLA= 1500 / (√3)×(.480)
FLA= 1,804 Amps

Put value of FLA in Isc formula-
Isc = 1804*100
5.75
Isc = 31373.91 amps

Facebook Page -
Рекомендации по теме
Комментарии
Автор

NICE EXPLANATION SO FAR IN U TUBE THANK YOU SO MUCH

jkj
Автор

Good and simple
Can u explain how to calculate no. Of earthing pit (station) for a given soil resistivity.
Thanks

parvezbamne
Автор

Great basic video for someone like me. Our plant has a pad mount transformer I can calculate using this.

davem
Автор

Is it SC between phase to phase? What about phase to Neutral?

bbe-belajarbersamaedward
Автор

What if the circuit breaker is on the primary side. Are you supposed to use the primary voltage instead of the secondary

karbonphiber
Автор

so based on this calculations we select MCCBs short circuit ratings?

asanmasraf
Автор

very well with one question... do u mean percentage impedance the voltage impedance since there is no percentage impedance on name plate of transformer it's percentage voltage impedance?

habtishasres
Автор

Same kA rating we will use for breaker also or their is Another formula for Switchgear

animishgodse
Автор

is this calculation same for three winding t/f because secondary side we have two windings .rating is changing for each winding then how can we caliculate

sivasankarp
Автор

Actual value is always less than what you calculated because you have to add the cable impedence and also generator impedence which when added will limit your sc current but never the less this is a good approximation in sizing your breakers

sharad
Автор

Or you can just divide your nominal voltage by the circuit Ze.
Also the definition of PSCC is not what you said, either.
A short circuit is the unintentional interconnection of the live conductors & you don’t double it unless it’s 3 phase.

goaway
Автор

Hello bro how we can calculate voltage impedance of transformer if we know only h 220/66kv t/f of 160mva nd also short circuit current find

Nirmalsingh-yyvn
Автор

In the last calculation Isc=1804*100, where did the 100 come from?

fjdan
Автор

This applies if the short circuit happens at the transformer secondary terminals

sharad
Автор

hey man, where you get the formula reference ? cz i can find anywhere

VinylChannel
Автор

What value is 100 at the last calculation

vinothkannan
Автор

In your formula to find the FLA, would you always multiply the kVsec by the square root of 3 (e.i., 1.73...) even if this were a single-phase system? How would this formula differ?

mattt
Автор

How to calculate short circuit current for motor?

aligohar
Автор

FLA =31373.91 AMP OR FLA = 31373.91 KA which is correct

muruganmurugan-rqjj
Автор

bhai formula conceptual nahi bataya aapne

kalimkhan