Kevin Compass joins HVAC School to give an overview of a transcritical CO2 refrigeration rack. He goes over its primary components during a commissioning procedure on a new system and talks a bit about charging a CO2 system.

CO2 has a triple point and a critical point within its operating range. The triple point is the lower threshold at which CO2 may exist as a solid, liquid, or vapor, so we have to keep the pressure above the triple point to prevent it from solidifying. (CO2 is often charged in the liquid state under pressure.) The critical point is at around 87 degrees Fahrenheit, and CO2 will become a transcritical fluid (which is neither liquid nor vapor and doesn't obey the rules of saturation). As a result, transcritical CO2 systems have a gas cooler instead of a traditional condenser. In conditions below 87 degrees, a gas cooler will function as a condenser; otherwise, it has to drop the pressure of the fluid to get it to condense.

The system in this video has a 3/8" charging line, which takes new refrigerant in the liquid phase; during charging, you have to watch your vessel pressure to make sure you don't hit the relief point.
The charging tanks have a dip tube to allow for charging in the liquid state. Once the sight glass stops flashing, we can disconnect the tank.

This system has a suction transducer, which measures pressure on the suction line. It also has a coil temperature sensor for defrost termination. On systems where the low-temperature and medium-temperature cases are on the same rack, the low-temperature compressors discharge into the suction line for the medium-temperature cases. The medium-temperature compressors discharge into the discharge line, which travels to the gas cooler. The compressors also have an oil system, which consists of a separator (coalescing, in this case), oil level regulators, and a reservoir (with an oil level sight glass and an oil level alarm). The reservoir is always maintained under pressure and vents off to the flash tank.

The low-temperature side of the system has an accumulator, transducer, and low-temp suction header. There is also a copper medium-temp discharge header. The high side of the system has a pressure gauge and a high-side relief valve, and the flash tank has relief valves, a bypass valve, a pressure gauge, transducers, a flash gas bypass valve, and an oil line bypass. Pressure is often measured and regulated using the bar scale, not PSI.

A heat reclaim valve allows the system to use compressor discharge gas for reheat at the main RTU. More pressure transducers limit the pressure drop to the reclaim condenser.

The gas cooler in this video has four ECMs and fans; it acts as a condenser when the temperature is below 87 degrees. The gas cooler also has a drop leg, which is the line between the condenser/gas cooler and the receiver. There is also a high pressure regulating valve and a flash gas bypass valve. Those valves work together to hold back and then vent off the gas to get the CO2 to condense back down; that keeps the flash tank at a certain pressure. The flash tank drops temperature and pressure at the same time.

The system also makes use of suction drier shells and hot gas injection, which injects hot gas into the medium-temperature suction side to regulate the superheat. If the superheat gets too high, the liquid injection valve helps de-superheat the medium-temp side.

The main electrical panel contains CPC (Emerson) controls, and the digital compressor controller uses pulse-width modulation. It also has a normal compressor contactor and a valve driver for the CO2, which manages communication between the valves. Boards monitor the dry contacts for the switches, sensors, and analog outputs. The main controller displays all of the display temperatures and the sensor data; each case has its own sensor and solenoid valve, which is managed and monitored by the main controller.

The two low-temperature compressors are scrolls, and the two medium-temperature compressors are of the semi-hermetic reciprocating variety. The rack is transcritical and compresses CO2. When the CO2 discharges out of the low-temperature compressors, it gets sent to the medium-temp suction header. That configuration reduces the compression ratio and improves capacity as a result. The compressors are controlled by a Danfoss VFD.

Podcast w/ Emerson on CO2:

Podcasts w/ Hill Phoenix on CO2:

Рекомендации по теме
Комментарии
Автор

THE ABSOLUTE SMARTEST AND INTERESTING GUY IVE EVER HEARD...HOLD MY ATTENTION AND YLUR SMART AZ HELL! APPRECIATE IT

HVACRDUDE
Автор

Awesome! I miss my rack days. Co2 is the new future

bmillwood
Автор

Used to have a small Coca Cola cooler for drinks. The Coca Cola company gave it to the restaurant owner. It used Co2 as refrigerant, and leaked. After swapping it with a R134a compressor, it works very good and no leaks any more (Over 2 years now). So high pressure means you have more potential leaks

UltraHydrophobiccoat
Автор

Wow, very interesting. The polar opposite of elegant simplicity. Rube Goldberg? Must be dramatically more efficient, or it wouldn’t be worth it. I would imagine that the upfront cost is high, and the service call costs will be even higher!

realvanman
Автор

Thank you very much for the effort of putting this together, guys! My head is saturated (!) now;) Have to watch it a few times to get it all in. Very interesting! You use a lot of the same components as us europeans, but the electrical standards are quite different.

aukanmeister
Автор

Very good thanks much the same system we have now being installed all over the uk in supermarkets

andrewsmith
Автор

I find it interesting when someone is trying to describe the trans-critical system; there are a lot of terms thrown about when trying to describe the state of the CO2 above the critical point. As said in the video it is neither gas/vapour or liquid. It is a supercritical fluid. A vapour would refer to a gas that is in equilibrium with a liquid phase, liquid is a subcooled state and gas is a superheated state. Supercritical is some kind of hybrid between liquid and gas and has properties of both. There is a mistake in the video to refer to CO2 above the critical point as 'transcritical' - it is not, it is supercritical. The system is transcritical because it operates on pressures that are both above and below the critical point and hence critical pressure. The system works across the critical pressure, hence 'trans' meaning across. 'Super' refers to above - i.e. supercritical is above the critical pressure.

elliot
Автор

A lot going on there. Don’t deal with co2 but awesome video. He’s a smart mechanic.

matthewcaldwell
Автор

We have them at our Grocery store I am service tech for. I was amazed how easy these are to work on.

danalan
Автор

thanks for the video! tough to imagine alot of us would get to see it this up and close with out the video

chrism
Автор

Thanks for all your efforts to provide us more and more technical specs...and knowledge.Alexis from Athens Greece!

alexl.
Автор

Thanks very much. Very useful and helpful for learning materials that are very hard to find and hardly known or understood.

HVACRServiceTech
Автор

Thank you & appreciated for sharing about CO2 Refrigeration. Need more further information of that systems such as sub critical system, about pipe thickness, power consumption compared to other systems etc...

azhariboerhan
Автор

Looks you got one expensive maintenance nightmare somebody will be married to that stuff .

chrisduhaime
Автор

Thanks guys, excellent overview! Just starting to get into CO2 systems myself.

john
Автор

This is the transducer for the transducer thats has another transducer for the main transducer

MrAnderson
Автор

Absolutely fantastic, great content, love how he explained how the rack works

davidshellenberger
Автор

New into c02 racks would love to get this dudes #. Got couple guys from hill phoenix that are pretty sharp but I’d like to work with this guy for a couple months !

jimmyp
Автор

The reason its called a transcritical rack is because its a cycle when the system goes above critical point co2 becomes a supercritical fluid and it transitions into the transcritical cycle. If you look at a enthalpy diagram we get a better idea of the cycles. Now when the system is below the critical point thus it runs in a subcritical cycle which is what were used to seeing because all other refrigerants have a much higher critical point.

codyeaton
Автор

Great video, seems though that energy consumption for the same application compared to HFCs is a lot higher! Should we take that under consideration, not to mention the installation costs.

manoskritikos