Continuity of CPC (R1 + R2) and Polarity of our 2 Way Lighting Circuit and Insulation Resistance

preview_player
Показать описание
Students training aid for testing continuity of the CPC and polarity of a 2 way lighting circuit. Full demonstration using a MFT Megger tester set on the ohms scale.

Demonstration shows how to set up your Megger MFT tester and carry out an insulation resistance test for a 2 way lighting circuit. Test voltage is 500V DC and the minimum acceptable value according to BS 7671 1 megaohms with further investigation when the reading falls below 2 megohms. Also shows and explains the need to switch both 2 way switches into the other on position and repeat the insulation resistance test.

Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.

You can follow me day by day on Facebook, Instagram and Twitter lookout for "GSH Electrical.

#GSHElectrical #Electricaltrainingvideos #electricaltesting
Рекомендации по теме
Комментарии
Автор

Absolute legend - Some trainers enjoy complicating this process, you make it as simple as it should be. Thank you.

danielsmith
Автор

Always clear your channel has taught me loads

ChernoBueno
Автор

Your videos are really helping me with my 2391 prep. thankyou!

dawber
Автор

Ive been at college 9 weeks doing evenings. weve lost 3 tutors so far with the help of your vieos i will pass thank you

kakhead
Автор

Thanks Gaz, it looks you didn’t take the lamp off while doing the insulation resistance test, would it be ok?

afshin
Автор

Another cracking video Gaz. These are gold dust! Thank you!

Minkywhispers
Автор

Brilliant training videoclip. Just as it should be in any respectable training session. Well done.

georgedumitrescu
Автор

Hi Gaz, in an installation wired in the loop in method with say the lives wired to the switches. If the end of line neutral and earth is in a different room than the end of line switch feed. Do you have to run a wander led between the two to obtain the highest possible r1 r2 reading. Or does the max resistance reading from a switch line to only the lights its controlling suffice? Thanks

andywoods
Автор

Would this testing be the same for two phase two way ? Because this is three phase ?

alfiemason
Автор

It is possible to show the method of examination by drawing

ammarbasrah
Автор

thanks for making this video it really helped me understand it

willmeadows
Автор

Hey, When you get the first reading for continuity, are both switches in the on position? Cheers

CptSmegpot
Автор

What about 0.38 reading, that is the highest reading, is that going in cert?

piotrf
Автор

is there a max value for R1+Rn ?? why do we just look at Zs for earth fault. Surely a live to neutral fault must also trip the circuit breaker fast ??

michaelcostello
Автор

How do you test a two way lighting circuit briefly

charliehenry