Calculate incident energy of arc flash - NFPA 70E

preview_player
Показать описание
Example shows how to use NFPA 70E annex D.4.3 to calculate the incident energy in cal/cm^2 of an arc flash incident on systems 208V through 15,000V. Formula works for all fuses and circuit breakers. Using the calculated incident energy one can determine the appropriate level of PPE for the potential arc flash hazard.
Рекомендации по теме
Комментарии
Автор

Thankyou Jonathan, the clearest explanation I have seen yet.

cliffharrington
Автор

Thank you by the explanation. My best regards from Brazil.

Railandi
Автор

Very nice video by Mr.Gracey, Could you please make video on Arc flash Boundary calculation

VikashKumar-tkde
Автор

Thanks Jonathan, jus one comment regarding the K1 factor value is (-0.555)

MrBelal
Автор

Hi Jonathan, Can you please clarify how you take D = 455 mm.

hellygondalia
Автор

Hi Jonathan, thank you for the clear explanation of the concept. In the calculation of your Normalized Incident Energy Level, the K_1 value used was a positive value (0.555), what would be the reason the value was positive in the equation? Thank you.

aremu
Автор

are these tables and values only found in that expensive nfpa book? i cant seem to find that exact table you used online