The HVAC contactor chattering and hang ups part 3

preview_player
Показать описание
A demonstration of the problems that can cause HVAC contactor chattering and hangups. Low voltage and armature wear are covered.
If you are a homeowner looking to repair your own appliance, understand that the voltages can be lethal, the fuels are highly flammable and high pressures are used. Know your limits.
Рекомендации по теме
Комментарии
Автор

Weak transformer would have low voltage when read with the contactor energized. Same with incorrect tap. Stat wire too small would also show up as low voltage. Absolutely a loose connection could cause chattering. I would think the contactor would have to be fairly massively oversized to cause chattering. Thanks for the thoughts, more to look for.
GFM

grayfurnaceman
Автор

Mine chatters when the ac is reaching the temp and ready to shut down. Is that a thermostat issue?

samuelm