Volume Flow Rate vs Mass Flow Rate w/ Jim Bergmann

preview_player
Показать описание

One of the most fundamental equations that drive the work we do is Q = mass x specific heat x ΔT. This is the equation we use to find BTUs. We can use a similar equation to figure out how many pounds of air we're moving if we already know how many CFM we're moving. Air density will affect the mass of the air and CFM, so that requires us to differentiate between standard CFM (SCFM) and the actual CFM (ACFM). ACFM differs from SCFM in that it factors in the effects of relative humidity, temperature, and barometric pressure on the mass of the air. Depending on the type of fan you have, you may really have a variable mass flow rate with a constant volume.

SCFM measurements are based on air at sea level, 68.3 degrees Fahrenheit, and 0% relative humidity (0.075 lbs/ft cubed). Higher relative humidity levels will reduce the density of the air, as water (H2O) is lighter than nitrogen (N2) and oxygen (O2), which make up most of our air. MeasureQuick's ACFM accounts for those humidity changes as well as pressure and temperature deviations from the sea-level, 68.3-degree standard.

Fans move a constant volume of air (SCFM), but the mass flow rate (ACFM) is much more variable based on location and climate. You can also use a psychrometric chart to help you with ACFM. The line of specific volume for 68.3 degrees and 0% relative humidity on a psychrometric chart also happens to be the inverse of the 0.075 lbs per ft cubed, which is the SCFM. (The ACCA manuals use SCFM for equipment design.)

ECMs work off RPM and torque; changes in air density affect the torque and affect ECM outputs. Since we're cooling the mass of the air, not the volume, it also helps to think about ACFM beyond ECM outputs.

Рекомендации по теме
Комментарии
Автор

Where did the 27.5 come from if your dividing 12000 by 30.24? Which equals 396. 🧐
Ok never-mind I see where it comes from…. I think. So, we are using the sensible heat equation (Btu/h=1.1xCFMxTD) rearranged the solve for TD. So, TD=Btu/(1.1xCFM). 12, 000/1.1x400=27.27*F…. Right?

victorhernandez
Автор

Thanks all of you to share great knowledge with easier and simple way.

So today i got the answered why 20* is rule of thumb, before it's scratches my head.

If our scfm is change or flow issues, so delta t will be change.

Safi.
Автор

Thanks Bryan and Adam. I was there when this was recorded, if you have the opportunity to attend a class at MeasureQuick, take advantage of it. Spending time with Jim and Joe, oh and waffles (can’t leave him out) is something I highly recommend.

edwardjanowiak
Автор

Thank you very Much for your Video !!!

texasstarniles
Автор

Fahrenheit ….

Is the ΔT in Fahrenheit the same as a ΔT in Celsius/Kelvin?

superoligarch_official
Автор

The mic quality starting at ~7 minutes is too much to make the rest of the video worth watching. It's short enough the content could probably be recorded again.

integraracer
Автор

Not seeing where this information is useful

michaelwest