Earth Continuity Testing: No Experience Needed!

preview_player
Показать описание
Testing electrical installations is crucial for ensuring safety, both in new setups and existing systems. In this video, created in partnership with Test Instrument Solutions, we dive into the fundamentals of continuity testing, focusing on protective conductors, including main and supplementary bonding.

Whether you're an electrical student, a seasoned professional needing a refresher, or preparing for an assessment, this video is for you. We'll cover everything from the basics to practical testing methods using a multifunction tester.

====================
Time Stamps ⏱
00:00 Testing is the most important area of electrical work
01:24 Why do we need to carry out the test?
02:16 What conductors need to be tested?
03:50 Setting up the MFT
04:50 We need to use the test methods from the On-Site Guide
06:15 Testing a lighting circuit
08:34 Testing a sub main
09:03 Protective bonding
10:45 Complete the training module
====================

#continuitytester #electricaltesting #electricalinstallation
Рекомендации по теме
Комментарии
Автор

Nice refresher. I studied Electrical thingies in college about 150 years ago, then did the C&G for part P testing about 10 years ago. But I can't remeber what I ate for tea yesterday

davewood
Автор

Good tutorial. I do like the idea of those adapters to facilitate a safer testing of light fittings

sergiofernandez
Автор

I think you should also remove the CPC from the earth bar for the circuit you are testing as you will not detect a break in the CPC if that circuit also has parallel paths to the point you are testing at

kevinpearson
Автор

An original R1R2 Link! Will be a collectors piece one day😁

wadelectrical
Автор

Test method 1 is not a correct way to do an R1 + R2 you need to disconnect the circuit cpc and connect it to the live and then do your test. The way you have shown you are testing parallel paths and getting incorrect readings. You should know better

DerekPodmore
Автор

Makes sense, but it's still daunting trying to workout when to use what method, mind you in only 1 weekend into my course.

fitnessabcvideo
Автор

Thanks for commenting, be sure to keep an eye out on the live stream tonight, 🤫🤫

joehammond
Автор

You explain things better than Gaz. You should make electrical installation testing series.

neowild
Автор

is calculation at 10:14 correct? not an expert and might be wrong but result looks wrong to me

alpaycelikel
Автор

Can you guess what will happen with washing machine that is connected to water that is used for ground, and there's a constant current leak that doesn't trigger breaker?
The washing machine water sensor will eventually go up in flames!
It might be not your circuit leaking, and it might be not your washing machine, but in apartment building that will eventually kill someone one way or the other

Gastell
Автор

How many resistance in earthing for best earthing

murarichaturvedi