filmov
tv
๐๐ ๐ ๐๐๐ ๐๐ซ๐จ๐ฆ ๐๐๐ก๐ซ๐จ๐๐๐ซ | ๐๐ฎ๐ญ๐จ๐ฆ๐๐ญ๐ข๐ ๐๐ฎ๐ซ๐ง๐๐ซ ๐๐จ๐ง๐ญ๐ซ๐จ๐ฅ ๐ฎ๐ง๐ข๐ญ | ๐๐จ๐ฆ๐ฆ๐ข๐ฌ๐ฌ๐ข๐จ๐ง๐ข๐ง๐ | ๐๐๐๐๐ข๐ง๐ ๐จ๐ ๐ญ๐ก๐ ๐ฉ๐๐ซ๐๐ฆ๐๐ญ๐๐ซ๐ฌ

ะะพะบะฐะทะฐัั ะพะฟะธัะฐะฝะธะต
๐๐
๐ ๐๐๐ ๐๐ซ๐จ๐ฆ ๐๐๐ก๐ซ๐จ๐๐๐ซ | ๐๐ฎ๐ญ๐จ๐ฆ๐๐ญ๐ข๐ ๐๐ฎ๐ซ๐ง๐๐ซ ๐๐จ๐ง๐ญ๐ซ๐จ๐ฅ ๐ฎ๐ง๐ข๐ญ | ๐๐จ๐ฆ๐ฆ๐ข๐ฌ๐ฌ๐ข๐จ๐ง๐ข๐ง๐ | ๐๐๐๐๐ข๐ง๐ ๐จ๐ ๐ญ๐ก๐ ๐ฉ๐๐ซ๐๐ฆ๐๐ญ๐๐ซ๐ฌ
โ๐๐๐๐ค๐ ๐ ๐๐๐๐ ๐ ๐๐๐๐ฃ๐ ๐ ๐๐ฆ๐๐ค๐๐ฃ๐๐๐ ๐
IFD 244
Gas burner monitoring with an ionization electrode. For grounded systems. With restart after a flame failure.
Commissioning
โ During operation, the 7-segment display shows the program status:
00 Start-up position
01 Waiting time
02 Safety time on start-up
04 Operation.
1. Close the manual valve!
2. Switch on the system.
3. Apply voltage to terminal 1.
4. Check the electrical installation.
5. Switch on the IFD.
โ The display indicates 00.
โ The IFD retains its switch position when the voltage is removed from terminal 1.
6. Start the program for the burner: apply voltage to terminal 3 โ the display indicates 0 1.
โ ฯ signal minimum ON time (terminal 3):
IFD..-3: 8 s
IFD..-5: 10 s
IFD..-10: 15 s
The times must be at least this long, otherwise the automatic burner control unit cannot monitor the burner.
โ Gas valve V1 opens, the burner ignites and the display indicates 02.
โ Ignition time tZ:
IFD..-3: 2 s
IFD..-5: 3 s
IFD..-10: 6 s
โ After the safety time tSA(3, 5 or 10 s) has elapsed, the IFD signals a fault. The display indicates a blinking 02.
7. Open the gas shut-off valve.
8. Reset the IFD by pressing the Reset/Information button.
9. Start the program for the burner: apply voltage to terminal 3.
โ The display indicates 02, the gas valve V1 opens and the burner ignites.
โ After the safety time tSA(3, 5 or 10 s) has elapsed, the display indicates 04.
โ The burner is in operation
Assistance in the event of malยญfunction
Fault Cause Remedy
The display blinks and indiยญcates 01 1. The IFD has detected an incorrect flame signal without the burner having been ignited (extraneous signal)
2. Flame signal through ceramic insulation Increase value of parameter 04 in order to adapt the switch-off threshold of the flame amplifier
Startยญup โ no ignition spark occurs โ the display blinks and
indicates 02 1.Gap between ignition electrode and burner head is too great
2. Ignition cable not contacting in the electrode adapter / ignition transformer
3. Ignition cable has short-circuited to ground
4. The ignition cable is too long
5. The ignition transformer is not connected to terminal 5 1. Adjust gap to max. 2 mm
2. Screw the cable on firmly.
3. Check installation, clean the ignition electrode
4. Shorten it to 1 m (max. 5 m)
5. Check the voltage supply to the ignition transformer.
Startยญup โ no gas supply the display blinks and indicates 02 1.The gas valve does not open
2. There is still air in the pipeline, for example after installation work or if the system has not been used
for a long period 1.Check voltage supply to the gas valve
2. โPurgeโ the pipeline and reset the system several times
Operation โ flame burning burner interrupted the display blinks and indicates 04 1.Short-circuit on the ionization electrode as the result of soot, dirt or moisture on the insulator
2. Ionization electrode not correctly positioned at the flame edge
3. Gas/air ratio incorrect 1.Clean Ionization electrode and positioned correctly
#Electrical
#Electronics
#technology
#repairing
#Services
#engineering
#tech
#howto
#testing
#machine
#industry
#maintenance
Reading off the flame signal and the parameters
๎ฌPress the Reset/Information button for 2 s. The display changes to parameter 01.
๎ฌRelease the Reset/Information button. The display stops at this parameter and indicates the related value.
๎ฌPress the Reset/Information button again for 1 s. The display changes to the next parameter. All parameters can be recalled one after the other in this way.
โIf the button is pressed only briefly, the display indicates what parameter is currently being displayed.
โThe normal program status is displayed again approx. 60 seconds after the last time the button is pressed.
Parameter list
Code Description
01 Flame signal (0โ25 ยตA).
04 Burner switch-off threshold (2โ20 ยตA).
12 Burner restart:0 = Immediate fault lock-out,1 = Restart.
14 Safety time during operation for gas valve (1; 2s).
22 Burner safety time on start-up (3; 5; 10 s).
81 Last fault.
82 Second to last occurring fault
83 Third to last occurring fault.
84 Fourth to last occurring fault.
.........
90 Tenth to last occurring fault.
๐๐ฝ๐ช๐ง๐ฃ๐๐ง ๐๐ก๐๐ข๐ ๐๐ค๐ ๐๐๐๐ฃ๐๐ก ๐๐๐๐จ๐ช๐ง๐๐ฃ๐ ๐ฌ๐๐ฎ (๐ฟ๐๐๐๐ฉ๐๐ก ๐ข๐ช๐ก๐ฉ๐๐ข๐๐ฉ๐๐ง ๐๐ฃ๐ ๐๐๐ฟ244 ๐๐ค๐ฃ๐ฉ๐ง๐ค๐ก๐ก๐๐ง)
#flamerod #signal #IFD244 #Burner #maxon #electrical #electronics #industry #detection #flame #trending #howto #electricvideo
๐ธ๐๐ก๐๐ข๐ ๐ง๐ค๐ ๐จ๐๐๐ฃ๐๐ก ๐ฉ๐๐จ๐ฉ๐๐ฃ๐ ๐๐ฎ ๐๐๐๐๐ฉ๐๐ก ๐ข๐ช๐ก๐ฉ๐ ๐ข๐๐ฉ๐๐ง
๐จโ๐ง๐๐๐ญ๐ค๐ฃ ๐ผ๐ช๐ฉ๐ค๐ข๐๐ฉ๐๐ ๐ฝ๐ช๐ง๐ฃ๐๐ง ๐๐ฅ๐๐ง๐๐ฉ๐๐ค๐ฃ
๐งฐ๐๐ช๐ฃ๐๐ฉ๐๐ค๐ฃ ๐ค๐ ๐ฉ๐๐ ๐๐ช๐ฉ๐ค๐ข๐๐ฉ๐๐ ๐๐ช๐ง๐ฃ๐๐ง ๐๐ค๐ฃ๐ฉ๐ง๐ค๐ก ๐ช๐ฃ๐๐ฉ ๐๐๐ฟ 244
โ๐๐๐๐ค๐ ๐ ๐๐๐๐ ๐ ๐๐๐๐ฃ๐ ๐ ๐๐ฆ๐๐ค๐๐ฃ๐๐๐ ๐
IFD 244
Gas burner monitoring with an ionization electrode. For grounded systems. With restart after a flame failure.
Commissioning
โ During operation, the 7-segment display shows the program status:
00 Start-up position
01 Waiting time
02 Safety time on start-up
04 Operation.
1. Close the manual valve!
2. Switch on the system.
3. Apply voltage to terminal 1.
4. Check the electrical installation.
5. Switch on the IFD.
โ The display indicates 00.
โ The IFD retains its switch position when the voltage is removed from terminal 1.
6. Start the program for the burner: apply voltage to terminal 3 โ the display indicates 0 1.
โ ฯ signal minimum ON time (terminal 3):
IFD..-3: 8 s
IFD..-5: 10 s
IFD..-10: 15 s
The times must be at least this long, otherwise the automatic burner control unit cannot monitor the burner.
โ Gas valve V1 opens, the burner ignites and the display indicates 02.
โ Ignition time tZ:
IFD..-3: 2 s
IFD..-5: 3 s
IFD..-10: 6 s
โ After the safety time tSA(3, 5 or 10 s) has elapsed, the IFD signals a fault. The display indicates a blinking 02.
7. Open the gas shut-off valve.
8. Reset the IFD by pressing the Reset/Information button.
9. Start the program for the burner: apply voltage to terminal 3.
โ The display indicates 02, the gas valve V1 opens and the burner ignites.
โ After the safety time tSA(3, 5 or 10 s) has elapsed, the display indicates 04.
โ The burner is in operation
Assistance in the event of malยญfunction
Fault Cause Remedy
The display blinks and indiยญcates 01 1. The IFD has detected an incorrect flame signal without the burner having been ignited (extraneous signal)
2. Flame signal through ceramic insulation Increase value of parameter 04 in order to adapt the switch-off threshold of the flame amplifier
Startยญup โ no ignition spark occurs โ the display blinks and
indicates 02 1.Gap between ignition electrode and burner head is too great
2. Ignition cable not contacting in the electrode adapter / ignition transformer
3. Ignition cable has short-circuited to ground
4. The ignition cable is too long
5. The ignition transformer is not connected to terminal 5 1. Adjust gap to max. 2 mm
2. Screw the cable on firmly.
3. Check installation, clean the ignition electrode
4. Shorten it to 1 m (max. 5 m)
5. Check the voltage supply to the ignition transformer.
Startยญup โ no gas supply the display blinks and indicates 02 1.The gas valve does not open
2. There is still air in the pipeline, for example after installation work or if the system has not been used
for a long period 1.Check voltage supply to the gas valve
2. โPurgeโ the pipeline and reset the system several times
Operation โ flame burning burner interrupted the display blinks and indicates 04 1.Short-circuit on the ionization electrode as the result of soot, dirt or moisture on the insulator
2. Ionization electrode not correctly positioned at the flame edge
3. Gas/air ratio incorrect 1.Clean Ionization electrode and positioned correctly
#Electrical
#Electronics
#technology
#repairing
#Services
#engineering
#tech
#howto
#testing
#machine
#industry
#maintenance
Reading off the flame signal and the parameters
๎ฌPress the Reset/Information button for 2 s. The display changes to parameter 01.
๎ฌRelease the Reset/Information button. The display stops at this parameter and indicates the related value.
๎ฌPress the Reset/Information button again for 1 s. The display changes to the next parameter. All parameters can be recalled one after the other in this way.
โIf the button is pressed only briefly, the display indicates what parameter is currently being displayed.
โThe normal program status is displayed again approx. 60 seconds after the last time the button is pressed.
Parameter list
Code Description
01 Flame signal (0โ25 ยตA).
04 Burner switch-off threshold (2โ20 ยตA).
12 Burner restart:0 = Immediate fault lock-out,1 = Restart.
14 Safety time during operation for gas valve (1; 2s).
22 Burner safety time on start-up (3; 5; 10 s).
81 Last fault.
82 Second to last occurring fault
83 Third to last occurring fault.
84 Fourth to last occurring fault.
.........
90 Tenth to last occurring fault.
๐๐ฝ๐ช๐ง๐ฃ๐๐ง ๐๐ก๐๐ข๐ ๐๐ค๐ ๐๐๐๐ฃ๐๐ก ๐๐๐๐จ๐ช๐ง๐๐ฃ๐ ๐ฌ๐๐ฎ (๐ฟ๐๐๐๐ฉ๐๐ก ๐ข๐ช๐ก๐ฉ๐๐ข๐๐ฉ๐๐ง ๐๐ฃ๐ ๐๐๐ฟ244 ๐๐ค๐ฃ๐ฉ๐ง๐ค๐ก๐ก๐๐ง)
#flamerod #signal #IFD244 #Burner #maxon #electrical #electronics #industry #detection #flame #trending #howto #electricvideo
๐ธ๐๐ก๐๐ข๐ ๐ง๐ค๐ ๐จ๐๐๐ฃ๐๐ก ๐ฉ๐๐จ๐ฉ๐๐ฃ๐ ๐๐ฎ ๐๐๐๐๐ฉ๐๐ก ๐ข๐ช๐ก๐ฉ๐ ๐ข๐๐ฉ๐๐ง
๐จโ๐ง๐๐๐ญ๐ค๐ฃ ๐ผ๐ช๐ฉ๐ค๐ข๐๐ฉ๐๐ ๐ฝ๐ช๐ง๐ฃ๐๐ง ๐๐ฅ๐๐ง๐๐ฉ๐๐ค๐ฃ
๐งฐ๐๐ช๐ฃ๐๐ฉ๐๐ค๐ฃ ๐ค๐ ๐ฉ๐๐ ๐๐ช๐ฉ๐ค๐ข๐๐ฉ๐๐ ๐๐ช๐ง๐ฃ๐๐ง ๐๐ค๐ฃ๐ฉ๐ง๐ค๐ก ๐ช๐ฃ๐๐ฉ ๐๐๐ฟ 244
ะะพะผะผะตะฝัะฐัะธะธ