Mastering Trane Chillers: Using Trane Techview

preview_player
Показать описание
📱The Chiller Guys Information Sharing Group:

This is a video on how to bind / CONNECT components on all Trane chillers that use a CH530 chiller controller using Techview Software. if you do not follow this procedure, the components will not link, and as a result will not operate.
You must use this procedure when changing any component on a Trane network, otherwise you will have communication issues, and the changed component wont work.

Some examples of the components you need this for on Trane chillers with the CH530 controller are:

1. Binding pressure transducers.
2. Binding temperature sensors.
3. Binding electronic expansions valves (EEV's).
4. Binding network controllers.

Some of the common models of chillers that require this binding procedure are:

Trane CVHE's
Trane CVHF's
Trane RTAA's
Trane RTAC's
Trane RTUD's
Trane RTWD's
Trane CGAM's
Trane CXAM's
Рекомендации по теме
Комментарии
Автор

Whats your worst experience with Trane?

TheChillerGuysHub
Автор

can we get same tracer TU software for UC 800 controller access purpose.
pls advise

sundarrajan
Автор

Maybe show what else you can do with techview. That would be cool for me, because all I’ve ever seen was binding.

hvac
Автор

Do Carrier, York, Mc Quay and other brands have the same procedure??

mallkomoha
Автор

Lots of motors shorted to ground and bad drives

T-dr
Автор

I am not representative of trane how can i use techview can u pls enlighten me

Apkaa