How to find Chiller Approach? | Evaporator and Condenser Approach | Animation | #hvac #hvacsystem

preview_player
Показать описание
Chiller Approach Value

We measure the efficiency value of a chiller to determine if it is working properly.

If the chiller efficiency value is abnormal, we need to measure the chiller approach value next.

The chiller approach value must be measured at the evaporator and condenser of the chiller.

By measuring, we can find out if there is a problem with the evaporator or the condenser.

Usually, the approach value is more likely to be higher in the condenser than in the evaporator.

This is because the water used in the condenser is at a higher temperature and the minerals in it dissolve in the coil, reducing the flow rate of the water flowing through it.

This reduces the heat transfer between the refrigerant and the water.

This will increase the approach value.

In addition, the water used in the condenser goes to the cooling tower, where it comes into contact with open air, causing a lot of dust to form in the water, which can also block the coil.

The descaling process must be used to remove dust and scale from the coil.

The condenser should be descaled once a year. The evaporator should be descaled once every 2 or 3 years.

The formula for finding the approach value of the evaporator is:

Evaporator Approach Value = Chilled Water Leaving Temperature – Refrigerant Temperature.

The evaporator approach value should be less than 3°F.

The formula for finding the approach value of the condenser is:

Condenser Approach Value = Refrigerant Saturation Temperature – Condenser water leaving temperature.

The Condenser Approach Value should be less than 4°F.

By watching this video in full, you will get a clear understanding of Chiller Approach.

Please support our channel by joining our channel and becoming a member and by using Super Thanks.

And don't forget to Subscribe to our Zebra Learnings Channel.

Thank you.

What is Saturation Temperature?

Chiller Efficiency Calculation
Рекомендации по теме
Комментарии
Автор

Very informative. I will use this as a resource in the future!

milonkill
Автор

A very important video. Thank you very much

lakshithabandara
Автор

Your every video is very informative ❤

faisal-hwcm
Автор

thanks for the VDO that is very good .then have the VOD about the Controller of frizzer

khansokha
Автор

You deserve a medal for this channel. Very informative and detail animation. Just curious on which refrigerant gas example you used in this video? Thank You :)

AmeerNaufalOmar
Автор

Whai is the cause why chiller approach is high?

sadikthebasicmaster
Автор

A very informative and detailed video. Can you recommend a good textbook for chiller plant maintenance and repairing? Thanks a lot!

AKK
Автор

How much value delta t evaporator water inlet and outlet sir which matter should be sir

prakashgotame
Автор

How to calculate Tr and how much temp should be given best cooling in chillers

srinumaradana
Автор

Condenser approach value you consider refrigerant saturation temperature, but evaporator approach value you consider refrigerant temperature. why you not consider refrigerant saturation temperature as well in evaporator approach value, can you explain?

jenish
Автор

Thank you for the information. Can you doing for precision air conditioning in the future?

CapeqKun
Автор

how we got leaving water value:42.7 F can you explain the same

Maddy_Pranit
Автор

Can please make comparison of dry expansion vs flooded evaporators prons and cons

hariharanradhakrishnan
Автор

Good day sir, it is possible to the chiller low refrigerant, run with capacity 100 high pressure?

sadikthebasicmaster
Автор

Air cooled chiller ka condenser ka kise nikalenge approach value …?😊

knowledgejourneyfun
Автор

Hi sir, can you explain in detail about chiller parameters.

harikumarmacharla
Автор

Bhai mughe bhi uae aana hai please batayein kaun se company mein kaam karaoo. Please bataiye ❤

samhaazratechnicalsupport
Автор

Water Leaving temp is going high or refrigerant temp will high tell me..

Water leaving temp-refrigerant temp or


refrigerant temp -
Water leaving temp

kaifravel
Автор

Good information. Are you teacher or from industry background?

parwindersinghwaraich
Автор

5:43 min your explanation correct, but your display is wrong greater than, less than

mahendranguru