Difference Between MCB and MCCB || MCB vs MCCB @TheElectricalGuy

preview_player
Показать описание
MCB Vs MCCB

What is MCB?
MCB or Miniature Circuit Breaker is an electromechanical device that protects an electric circuit from an overcurrent. The overcurrent in an electrical circuit may result from short circuit, overload or faulty design.

1. Current rating – Amperes
2. Short Circuit Rating – Kilo Amperes (kA)
3. Operating Characteristics – B, C, D, Z or K Curves

What is MCCB ?
A molded case circuit breaker (MCCB) is a type of electrical protection device that is used to protect the electrical circuit from excessive current, which can cause overload or short circuit.

Thank You
Arun Gupta

══════⊹⊱≼≽⊰⊹═════════⊹⊱≼≽⊰⊹══════

Hindi Channel @Electrical Technician

2nd Channel @electrical Wiring School

Short Video @electrical technician Shorts

TELEGRAM :

FACEBOOK : @electricaltechnical

INSTAGRAM : @electricaltechnician02

══════⊹⊱≼≽⊰⊹═════════⊹⊱≼≽⊰⊹══════

My gadgets for YouTube 📺

Camera 📸 For video Recording

Mic 🎤 For Sound Recording

Tripod Stand

Overhead Stand For Recording

══════⊹⊱≼≽⊰⊹═════════⊹⊱≼≽⊰⊹══════

Electrical Device For your Home which you Should Have

Wi-Fi Control Smart Plug top

Multimeter for electrician

Water Level Controller

Motor Starter

Toolkit For Electrician

══════⊹⊱≼≽⊰⊹═════════⊹⊱≼≽⊰⊹══════

Related Video which you must watch

MCB Vs MCCB Vs RCCB Vs ELCB Vs RCBO

Type of MCB

Type of Switch used in Industry

Wi-Fi MCB

Distribution Board Connection

MCB Changeover Switch

#mcb #mccb #electrical #electrician
Рекомендации по теме
Комментарии
Автор

Nice, next video show us types changeover

charleswambia
Автор

Good information but know that there's MCB of up to 120A as well as MCCB of 32A.

krisanwana
Автор

A few mistakes I've noticed

- MCB's nominal current goes anywhere from 0.5A to 125A
- MCCB's nominal current goes from 16A to 3200A or even 4000A
- MCBs can absolutely feature auxiliary or alarm contacts and/or a shunt trip. Schneider's A9A26909 is an auxiliary+alarm for iC40/iC60 MCBs, for example
- the breaking capacity of an MCB goes anywhere from 4.5kA to 100kA. Schneider's iC60L and NG125 go up to 100kA if I recall correctly.
- MCCBs also exist in 1-pole and 2-pole configuration, although they're quite rare
- 7:34 The Ics is the current that can be safely and repeatedly interrupted by the breaker. In your example MCCB, you can break 35kA (=Icu) but the breaker will probably be toast after it. If you don't want it to be toast, stick to 25kA (=Ics) or lower and you'll be fine.

rosskrt
Автор

Nowadays 2 Pole MCCB Also available in Market. MCCB Rating starts From 32 Amps. Another Diffarance between MCCB & MCB is that there is a Single switch or Mechanism in MCCB to On or Off the device but in case of 2, 3&4 Pole Mcb there are separate swithes & Separate Tripping Mechanism and All Separate MCBs fixed commonly with revetting rods, Swithes also collaborated with Common Rod.🙏

Dayanand
Автор

Small corrections : 1) There is a shunt trip option for some types of MCB, 2) Current ratings for MCCB start from 40A not 100A and go up to 3200A not just 2500A. 3) Most important differences between MCB and MCCB is (as you stated) the larger Icu, and DURABILITY (service cycles).

Metalloys
Автор

Very good class. Please make a video related IEC and NEMA electrical standard

mohammedrafeeq
Автор

Super dude, subrscribed, , thanks for new learning to me

johnvinoth
Автор

Good video. MCB also can be provided with aux. Contacts

harshalarkadi