PS98 Sequence Networks of Earthing transformer

preview_player
Показать описание
Lectures on Power Systems By Dr. Tirupathiraju Kanumuri, Assistant Professor, NIT Delhi

Link for Material

Link for Lectures on Synchronous Machines:
Link for Lectures on Special Electrical Machines:
Lectures on Induction Motors:
Lectures on Basic Electrical engineering:
#SequenceNetworksofEarthingtransformer
#zeroSequenceNetworkofEarthingtransformer
#zeroSequenceimpedanceofEarthingtransformer
Рекомендации по теме
Комментарии
Автор

Thank you for providing comprehensive lecture

sunjang
Автор

Good video. We have an 11kV earthing transformer with an earthed star connected primary winding and a secondary winding with a broken delta connection with a resistor that limits the primary winding current to 60A. How do you determine/model the zero sequence impedance of a broken delta connected transformer. thanks

paulthompson
Автор

Hi,
Thank you for your nice lectures ...
To enhance this lecture technically more correct, we can go by taking industrial powersystem as an example (where it ll be YNd1/11 - step down trafo ... and Delta side will be grounded via grounding trafo... )
and to add one more point, Generating stations usually have YNd1/11 (step up trafos)
:)

kmnkr
Автор

Sir what happens if there is no path for circulating currents.

MANOJKUMAR-mbuw
Автор

Thanks a lot sir for the sequence diagram for earthing transformer..these kind of informative videos helps a lot in our work field....sir i have 1 more request..can u provide sequence diagram of autostransformer having delta as tertiary stabilising winding(YNyn0d11 as well as Yy0d11)?

sanjibkumardas
Автор

Sir can u provide a sequence network of 3 phase transformer consists of HV star, intermediate volatage star and lv voltage delta for example 220/132/33 KV transformer

jyotishasikhya
Автор

Hi Sir, its a very informative lecture. I have a question, can we convert IT Earthing network to TN using Zigzag transformer at LV side (415V), but we cant use Earthing resistor in neutral of Zigzag transformer. Is it possible?

mallikarjunayh
Автор

Hi, thanks for these kind of videos.

1- How can we calculate zero sequence impedance of zig-zag transformer ? As you mentioned, during phase to ground fault, only impedance that effect to our ground fault short circuit current is zero sequence of zig-zag transformer. Also other component will be effect on the path of that faulty line.

System Voltage (L-L)=10, 5Kv
Irated/phase=100A
Short Circuit current in neutral=1000A, 10sec
Ohm/per phase = 18, 2 ohm/phase

2- On ETAP program, below informations are needed. But I could not understand these value is ohm or pu values of zero sequence. Even I am not sure these values zero or not ? If I put ohm/per phase values, ground fault is going to limit from 15kA to 2kA. I do not know how it calculate ? Do you have any advice ?

Impedance;
Ohm= --> Etap Help page said that ''Enter grounding resistor or reactor in ohms''
X/R= --> Etap Help page said that ''Enter the grounding transformer X/R ratio''