Understanding ampacity and temperature rating of different wire

preview_player
Показать описание
let me how if you want me to dive deeper into this subject
Рекомендации по теме
Комментарии
Автор

allowable ampacity (AA) is permitted to be the 90deg when temperature correction factor necessitates application
#2 THHN will have AA to be 130A * (say 0.96) Temp Correction Factor for hotter ambient = 124.8A to be connected to a 75deg terminal >> than by using THW at 115A, even though when no correction factor both THW & THHN have AA of conductor ampacity (CA) of 115A to a 75 deg terminal ;

this is the advantage of using THHN in hot environments which the NEC permits .

leusmaximusx
Автор

Good job, but not true with the number 8 on 50 amp circuit. For terminals rated 60 deg you shouldn’t use number 8 but 75 degree you’re good if the terminals call for 75 degrees. Right in the code tables 310

ryanbowles
Автор

I'm sorry not trying to be rude but I couldn't understand half of what you were saying. You slur your words a lot