How to make GOOSE Between DIGSI 4 and DIGSI 5 | HOW TO MAKE GOOSE IN DIGSI 5

preview_player
Показать описание
In this section I am going to show you how to make goose Between Digsi 4 and Digsi 5
How to Create IEC61850 File in DIGSI 5 click the below link

For this SLD is for Main bus and Transfer bus schematic.
I am going to Take Transformer bay BCU relay
I need All other Q88 open status and Bus coupler Isolator and Breaker close and open status.
Since For this bay Q88 ( transfer isolator ) close and open has this interlock.
If your going to making hard wire for all this status then we have to make more Binary input to avoid this I am going to use goose.
Since for Bus bar protection all Q88 status and bus bar isolator and breaker status already had in Busbar relay.
So I am going to take goose signal from busbar relay.
Рекомендации по теме
Комментарии
Автор

Hi Barani, Thanks a lot for your Digsi Support Videos. I would like to clarify a doubt. I have one Siprotec 5 connected in a IEC 61850 network, but its doesn´t update the time according the GPS. The F.O connected to it is ok, but I need to change the parametrization for time inside the digsi. Do you know whether this modification can affect the IEC communication between device and Scada?

marcelocabralarruda
Автор

Hi, I want to configure remote end signals in my relay 7SL86 (some status and protection signals). How to configure them, can you please clear. Thanks

beautifulireland_europe
Автор

Hi bro, thank for ur video it’s more useful to us, pls make one video for DIGSI 4 signals goes to DIGSI 5 BCU, I tried but I couldn’t get external signal which I already created in information routing in Destination portion.,

sureshboopalan
Автор

Thanks, choose same IED location also can do

boweiluo